PAS5600 Wireless Integrated Vibration and Temperature Transmitter


## System Features

It is a truly fully wireless condition monitoring device requiring zero cable laying, enabling unprecedented ease of installation and maintenance for online monitoring.


### High Professionalism

Designed for petrochemical and coal mine sites with full Exia intrinsic safety explosion-proof construction. Simple installation and construction eliminate the need for bulky flameproof enclosures.


Low power consumption design with IP66 protection rating.


Professional remote diagnostic services available.


### Comprehensive Monitoring Functions

Intelligent monitoring solution integrating vibration, temperature and rotational speed measurement to monitor both steady-state and unsteady-state equipment.


Complete monitoring charts (overview diagram, time-domain waveform, spectrum analysis, trend analysis, waterfall plot, order analysis, etc.)


Detailed data lists (characteristic value list, signal statistics table, alarm list, maintenance record log, etc.)


### Advanced Data Storage

Multi-trigger data saving strategies including synchronous acquisition, rotation speed-triggered acquisition and alarm-triggered acquisition.

Intelligent data storage prevents loss of monitoring data caused by network disconnection or power failure.


### Excellent Scalability

Diverse communication options: Ethernet, optical fiber, Wi-Fi and other communication methods to adapt to various industrial sites.


## Vibration Measurement Parameters

Vibration range: ±50 g

Linearity: 1%

Frequency response: ±3 dB

Sampling frequency: 1280 Hz ~ 51.2 kHz

Analysis frequency options: 500 Hz, 1 kHz, 2 kHz, 5 kHz, 10 kHz, 20 kHz

Maximum long waveform sampling length: 2M

Configurable sampling lengths: 1K, 2K, 4K, 8K, 16K, 32K, 64K, 128K


## Temperature Measurement Parameters

Temperature measurement range: -40 ~ 125 ℃

Temperature measurement accuracy: ±1 ℃ (-40 ℃ ~ 125 ℃)


## Electrical and Structural Parameters

Power supply: Lithium thionyl chloride battery

Communication standard: 2.4 GHz IEEE 802.15.4

Transmission distance: 300 meters with no interference and unobstructed line of sight

Dimensions: 46 mm × 94 mm (diameter × height)

Contact surface diameter: 19 mm

Weight: 188 grams

Mounting thread size: Metric M6

Mounting methods: Bolt fastening or metal adhesive bonding


## Environmental Parameters

Operating temperature: -40 ~ 70 ℃

Ingress protection rating: IP67

Explosion-proof grade: ExiaIICT4 (suitable for Zone 0, Zone 1 and Zone 2 hazardous areas)